-
The cells used
in photovoltaic modules convert all wavelengths within the visible light
spectrum to DC electricity but are optimised for the wavelengths that
occur most commonly.
-
In
the
UK we receive approximately five times more energy from the sun in June
& July than we do in December & January.
-
The
unit
of energy for insolation (incoming solar radiation or energy from the sun)
is the kilowatt hour per square meter per day (kWh/m²/day). The UK
mainland receives at best a mean daily insolation of around 5kWh/m²/day
and at worst a mean daily insolation of around 1kWh/m²/day. As these are
mean values it must be anticipated that actual values will at times be
higher or lower than these figures.
-
The
unit
"kWh/m²/day" is also referred to as the "equivalent
sunshine hour" (ESH).
-
For
peak
performance a solar module should face the brightest part of the sky. Most
modules are installed at a fixed azimuth and tilt angle in order to
maximise their annual energy output.
-
Tracking
systems
may be utilised to improve system performance (by up to 30% for 2-axis
tracking) but are expensive and a potential source of unreliability in
systems which would otherwise have no moving parts.
-
At
high
tilt angles most modules are self-cleaning, however, if bird droppings are
likely to be a problem then "bird spikes" should be employed to
disuade birds from perching along the top of the module. This is most
effectively achieved by drilling holes along the module support frame's
top edge and passing plastic cable ties through them. Once tightened the
end that would normally be cut off is left pointing upwards.
-
Solar
modules
are made up of many "cells" manufactured from various forms of
silicon. The greater the light intensity falling on these cells the
greater the current produced (light intensity and output current are
proportional). However, the voltage produced is not proportional to light
intensity but rises very quickly in low light ensuring that charging can
take place.
-
Partial
shadowing
of a module should be avoided at all costs as the effect is a
disproportionate reduction in power output. The cells in a module are in
long series strings, where the current passing through each cell is the
same, the effective output is thus determined by the cell with the lowest
output.
DESIGN
& INSTALLATION
In order to
determine the size of a suitable module to meet a specific load requirement we
need the following information:
-
LOAD - worst
case daily figure expressed in ampere hours per day (Ah/day).
-
VOLTAGE -
nominal
system voltage (12, 24, 48, etc).
-
ESH -
the
worst case equivalent sunshine hours per day value must be selected
for the site, azimuth and tilt angle chosen.
Using this information
you can calculate the System Amps (SA) using the simple formula below
(where SA=the module(or array) current at peak power - Ipp). A safety
factor of 1.2 is incorporated to account for various losses including
cabling, diodes, battery charge efficiency, module production
tolerances and ageing.
Once the SA has
been calculated then a module (or modules) with the required Ipp can
be specified. The total number of modules required in the system is
also a function of the required nominal voltage. The current
requirement is met by the number of modules in parallel whilst the
voltage requirement is met by the number of modules in series.
AZIMUTH
- Modules should face true south in the Northern Hemisphere and
true north in the Southern Hemisphere.
TILT
ANGLE - For systems providing power all year round with a
fixed module the appropriate tilt angle above horizontal may be
chosen from the following table in order to maximise the annual energy
output.
SITE
LATITUDE degrees
|
TILT ANGLE above horizontal in degrees
|
0-4
|
10
|
5-20
|
Site
latitude + 5 degrees
|
21-45
|
Site
latitude + 10 degrees
|
46-65
|
Site
latitude + 15 degrees
|
66-75
|
80
degrees
|
Seasonal
improvements can be achieved by reducing the angle in summer (flatter)
and increasing it in winter (steeper). Solar Navigator tracks
the Sun and weather providing automatically adjusts its wings to the
optimum angle.
Maximum
Height Of Sun World Wide
The
table below is for the maximum angle the sun will reach at noon local
time
|
Mid
|
Mid
|
Mid
|
Mid
|
Mid
|
Mid
|
Mid
|
Mid
|
Mid
|
Mid
|
Mid
|
Mid
|
Latitude
|
JAN
|
FEB
|
MAR
|
APR
|
MAY
|
JUN
|
JLY
|
AUG
|
SEP
|
OCT
|
NOV
|
DEC
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60°N
|
10
|
16
|
26
|
40
|
49
|
53
|
51
|
44
|
33
|
21
|
12
|
8
|
55°N
|
14
|
22
|
31
|
45
|
54
|
58
|
56
|
49
|
38
|
26
|
18
|
12
|
50°N
|
19
|
27
|
36
|
50
|
59
|
63
|
61
|
54
|
43
|
31
|
22
|
17
|
40°N
|
29
|
37
|
47
|
60
|
69
|
74
|
71
|
64
|
53
|
41
|
32
|
27
|
30°N
|
40
|
47
|
56
|
70
|
79
|
83
|
81
|
74
|
63
|
51
|
42
|
37
|
20°N
|
49
|
58
|
66
|
80
|
89
|
87
|
89
|
84
|
72
|
61
|
52
|
47
|
10°N
|
59
|
67
|
76
|
90
|
81
|
77
|
79
|
86
|
83
|
71
|
62
|
57
|
0°
|
69
|
77
|
87
|
80
|
71
|
67
|
68
|
76
|
86
|
81
|
72
|
67
|
10°S
|
79
|
87
|
84
|
70
|
61
|
57
|
59
|
66
|
77
|
89
|
82
|
77
|
20°S
|
89
|
83
|
74
|
61
|
51
|
47
|
49
|
56
|
67
|
79
|
88
|
86
|
30°S
|
80
|
72
|
64
|
50
|
41
|
37
|
40
|
46
|
57
|
69
|
78
|
82
|
-
BATTERY
SIZING - The battery in a photovoltaic system is of
equal importance to any other element, if it fails the system
fails. For a continuous load it serves to provide electrical power
every night when module output is zero as well as during days when
module output is below the average for the time of year. For
systems providing power all year round the size of a lead acid
battery is calculated taking the following into account:
-
1) Worst
case daily load.
-
2)
Site
latitude - higher latitudes generally have longer periods of below
average insolation during the winter months and thus require
greater reserve capacity.
-
3)
Temperature derate - battery capacity is reduced at low
temperatures.
-
4) Depth
of discharge - the deeper we discharge a battery the fewer cycles it
will give to this depth during its life.
-
REGULATION
& BLOCKING DIODES - If at any time during the year
the daily module output exceeds the daily current drawn from the
battery then a regulator is required. If the module is to remain
permanently connected to the battery (except during periods of
regulation) then a blocking diode is required. All BECO regulators
incorporate a blocking diode.
CABLE SIZES
- The following table indicates the current carrying capacity of
various cable cross sectional areas:
|
12v
SYSTEMS - 0.25v maximum drop
|
CSA
(mm) AWG
|
1.3/16
|
2.0/14
|
3.2/12
|
5.1/10
|
8.5/8
|
13.5/6
|
21/04
|
|
Max
current for 5m length
|
1.5
|
3.0
|
5.0
|
7.5
|
12.0
|
18.0
|
29.0
|
Max
current for 5m length
|
0.5
|
1.5
|
2.5
|
3.5
|
6.0
|
9.0
|
14.5
|
Max
current for 5m length
|
n/a
|
1.0
|
1.5
|
2.5
|
4.0
|
6.0
|
9.5
|
|